< 上一个 | 内容 | 下一个 >

10.4 Metering function set


10.4.1 Overview


The Metering function set provides interfaces to exchange commodity measurement information such as reading types and meter readings between HAN devices. Examples of Meter Flows and XML payloads are listed in Annex C.


Each Metering function set server may have a UsagePointList resource containing resources for local meters and metering data mirrored for other devices. One possible scenario is that two electric meters exist in a HAN. Both have a UsagePoint resource. Electric Meter #1 (e.g., ESI integrated) has a UsagePoint list which contains for example /upt/0 (meter itself) and /upt/1 (mirrored gas meter). Electric Meter #2 also has ESI integrated and has, for example, a /upt list which contains only one instance /upt/0 (meter itself) but no other meter mirrored to it. Since both UsagePoints are visible, a HAN device that does service discovery will find both UsagePoint servers and it then has to decide which UsagePoint server to query based on server’s information. Note that although there are two /upt/0 instances in this case, they are two different servers with different hostnames and/or IP addresses.


10.4.2 List ordering


Table 39 —Metering list ordering


Resource name

Primary key

Secondary key

Tertiary key

UsagePoint

mRID

(descending)

N/A

N/A

MeterReading

mRID

(descending)

N/A

N/A

ReadingSet

timePeriod.start (descending)

mRID

(descending)

N/A

Reading

localID

(ascending)

consumptionBlock

(ascending)

touTier

(ascending)


10.4.3 Application guidelines/behavior


The Metering function set resource hierarchy starts with a list of Usage Points. A Usage Point is an abstraction for a point of exchange. This could be represented as a physical meter or a fixed load like a street lamp or a virtual metering point as accomplished with transformer or line loss compensation algorithms. Each Usage Point then has one or more Meter Readings. Meter Readings serve as an aggregation for the ReadingType, a possible Reading and possible Reading Sets. The ReadingType is constructed based on subsets and extensions of IEC 61968-9 Annex C, Reading Types. Only relevant IEC fields are listed in the XML Schema described in the supplemental material of IEEE Std 2030.5 and IEEE Std 2030.5 UML model. It may be beneficial for implementers to obtain a copy of this IEC document in order to better understand the meanings and uses of the IEC 61968-9 Reading Types. See the following text for uses of the ReadingSets and Readings.


In the following text, the terms current and present refer to the values at the time the resource is read. In terms of ReadingSets, the terms refer to the ReadingSet that is being built/filled at the time of reading. While a ReadingSet is in this state, ReadingSet.timePeriod.start SHALL be when the ReadingSet starts recording its first value and that ReadingSet.timePeriod.duration SHALL grow each time the ReadingSet is updated. The ReadingSet.mRID field SHALL be assigned a value of 0xFFFFFFFFFFFFFFFFFFFFFFFF[XXXXXXXX] (Where [XXXXXXXX] is replaced by the

manufacturer’s PEN) while the data is being recorded and changed to an appropriate mRID when the ReadingSet is complete.


A Metering function set instance that provides instantaneous demand data SHALL serve a Meter Reading resource (and subordinate resources) with the following properties:


SHALL contain a ReadingTypeLink element that points to a ReadingType resource that matches the InstantaneousDemand definition from Table 40.

SHALL contain a ReadingLink element that points to a Reading resource that contains the instantaneous demand value.

SHALL not contain a ReadingSetListLink element.

A Metering function set instance that provides summation delivered data SHALL serve a Meter Reading resource (and subordinate resources) with the following properties:


SHALL contain a ReadingTypeLink element that points to a ReadingType resource that matches the SummationDelivered definition from Table 40.

The ReadingType resource SHALL specify the number of TOU tiers and/or consumption blocks, if any, that the metering instance provides.

SHALL contain a ReadingSetListLink element that points to a ReadingSetList resource.

When metering data is present, the ReadingSetList SHALL contain at least one ReadingSet resource, which corresponds to the present summation delivered data.

The ReadingSet resource SHALL contain a ReadingListLink element that points to a ReadingList resource. The ReadingList resource SHALL contain (number of TOU tiers

+ 1) multiplied by (number of consumption blocks + 1) Reading resources. Note that if the number of TOU tiers is 1, using a value of 1 instead of 0 will be less efficient and is DISCOURAGED.

The Reading resources in the ReadingList SHALL correspond to the summation delivered value for each combination of consumptionBlock = 0..(number of consumption blocks) and touTier = 0..(number of TOU tiers).

The Reading for (consumptionBlock = 0, touTier = 0) SHALL correspond to the total summation delivered.

The Reading for (consumptionBlock = x > 0, touTier = 0) SHALL correspond to the Block x summation delivered (across all TOU tiers).

The Reading for (consumptionBlock = 0, touTier = y > 0) SHALL correspond to the TOU Tier y summation delivered (across all consumption blocks).

The Reading for (consumptionBlock = x > 0, touTier = y > 0) SHALL correspond to the consumptionBlock x, touTier y summation delivered.

SHALL contain a ReadingLink to a Reading resource that contains the present summation delivered, which is semantically equivalent to the Reading for (consumptionBlock = 0, touTier = 0) for the present ReadingList.

A Metering function set instance that provides summation received data, maximum demand delivered data, maximum demand received data, and/or other reading type data that utilizes TOU tiers and/or consumption blocks SHALL serve a Meter Reading resource (and subordinate resources) as per the rules for Summation Delivered above, but with the Reading Type resource matching the appropriate definition in Table 40, and with the Reading values corresponding to the appropriate data type.


A Metering function set instance that provides interval data SHALL serve a Meter Reading resource (and subordinate resources) with the following properties:


a) SHALL contain a ReadingTypeLink element that points to a ReadingType resource that matches an Interval data definition from Table 40.


1) The ReadingType resources SHALL specify the intervalLength that is the default for the intervals contained in the ReadingList resource.


b) SHALL contain a ReadingSetListLink element that points to a ReadingSetList resource.


1) When metering data is present, the ReadingSetList SHALL contain at least one ReadingSet source, which MAY correspond to the present Interval Block data (the one currently being filled).


i) The ReadingSet resource SHALL contain a ReadingListLink element that points to a ReadingList resource. The ReadingList resource SHALL contain Reading resources each of which represents a portion (interval) of the timePeriod of the ReadingSet.

ii) If the duration in the timePeriod of the Reading is not equal to the intervalLength specified in the Reading Type the timePeriod SHALL be included in the Reading.

c) SHALL NOT contain a ReadingLink resource.


Table 40 provides a list of common Reading Type Definitions with related fields listed.

IEEE Std 2030.5-2018

IEEE Standard for Smart Energy Profile Application Protocol


Table 40 —Reading types



ReadingType Element

accumulationBehavior

calorificValue


commodity


conversionFactor


dataQualifier


flowDirection


intervalLength


kind


numberOfConsumptionBlocks


numberOfTouTiers


phase


powerOfTenMultiplier


subIntervalLength


suppyLimit


tieredConsumptionBlocks


uom

Instantaneous demand

12


1



1

E

8




O

E


E

38

Summation delivered

9


1



1

E

12

O

O


O

E



72

Summation received

9


1



19

E

12

O

O


O

E



72

Maximum demand delivered

6


1


8

1

O

8

O

O


O


E


38

Maximum demand received

6


1


8

19

O

8

O

O


O


E


38

Intervals delivered

4


1



1

O

12




O

E


E

72

Intervals received

4


1



19

O

12




O

E


E

72

Blank cells indicate not used for the given ReadingType name. May be used for other ReadingTypes. “E” indicates they are not to be used for this class of ReadingType no matter commodity.

“O” indicates that there could be value specified.

Note the values in this table are provided as examples of possible electricity meter ReadingTypes. A metering instance must set these values as appropriate for its commodities. For example, SummationDelivered may apply to gas or water if the commodity is “NaturalGas” with uom value of 42(m3) or “PotableWater” with uom value of 128 (U.S. gallon) or 134 (liters). Other commodities are to indicate appropriate UOMs. A combination of uom and powerOfTenMultiplier are used to represent units with different magnitudes, for example kWh would be represented as uom of 72 and a powerOfTenMultiplier of 3. As for fractional Wh readings, 0.012 Wh can be expressed as powerOfTenMultiplier = -3, uom = 72, and value = 12.

Relevant UOMs and other reading type fields are listed in the XML schema described in the supplemental material of IEEE Std 2030.5.


10.4.4 LogEvents


This subclause includes definitions of all LogEvents that may be raised by the Metering function set. The LogEvent names and codes are summarized in Table 41.


Table 41 —Metering LogEvents


LogEvent name

LogEvent code

LogEvent description

UPT_CHECK_METER

0x00

SHOULD be issued when check meter alarm occurs

UPT_CHECK_METER_RTN

0x01

SHOULD be issued when check meter alarm clears

UPT_TAMPER_DETECT

0x02

SHOULD be issued when a tampering is detected

UPT_TAMPER_DETECT_RTN

0x03

SHOULD be issued when a tampering detect clears

UPT_POWER_QUALITY

0x04

SHOULD be issued when power quality alarm occurs. It is a generic power quality event code.

UPT_POWER_QUALITY_RTN

0x05

SHOULD be issued when power quality alarm clears

UPT_ LEAK_DETECT

0x06

SHOULD be issued when a leak is detected

UPT_LEAK_DETECT_RTN

0x07

SHOULD be issued when a leak detect clears

UPT_SERVICE_DISCONNECT

0x08

SHOULD be issued when service is disconnected

UPT_SERVICE_CONNECT

0x09

SHOULD be issued when service is connected

UPT_SERVICE_LIMITED

0x0A

SHOULD be issued when service limited alarm occurs

UPT_SERVICE_LIMITED_RTN

0x0B

SHOULD be issued when service limited alarm clears

UPT_LOW_VOLTAGE_L1

0x0C

SHOULD be issued when low voltage L1 occurs

UPT_LOW_VOLTAGE_L1_RTN

0x0D

SHOULD be issued when low voltage L1 clears

UPT_HIGH_VOLTAGE_L1

0x0E

SHOULD be issued when high voltage L1 occurs

UPT_HIGH_VOLTAGE_L1_RTN

0x0F

SHOULD be issued when high voltage L1 clears

UPT_LOW_VOLTAGE_L2

0x10

SHOULD be issued when low voltage L2 occurs

UPT_LOW_VOLTAGE_L2_RTN

0x11

SHOULD be issued when low voltage L2 clears

UPT_HIGH_VOLTAGE_L2

0x12

SHOULD be issued when high voltage L2 occurs

UPT_HIGH_VOLTAGE_L2_RTN

0x13

SHOULD be issued when high voltage L2 clears

UPT_LOW_VOLTAGE_L3

0x14

SHOULD be issued when low voltage L3 occurs

UPT_LOW_VOLTAGE_L3_RTN

0x15

SHOULD be issued when low voltage L3 clears

UPT_HIGH_VOLTAGE_L3

0x16

SHOULD be issued when high voltage L3 occurs

UPT_HIGH_VOLTAGE_L3_RTN

0x17

SHOULD be issued when high voltage L3 clears

UPT_OVER_CURRENT_FORWARD_L1

0x18

SHOULD be issued when overcurrent L1 occurs in the forward (consumed by premises) direction

UPT_OVER_CURRENT_FORWARD_L1_RTN

0x19

SHOULD be issued when overcurrent L1 clears in the forward (consumed by premises) direction

UPT_OVER_CURRENT_FORWARD_L2

0x1A

SHOULD be issued when overcurrent L2 occurs in the forward (consumed by premises) direction

UPT_OVER_CURRENT_FORWARD_L2_RTN

0x1B

SHOULD be issued when overcurrent L2 clears in the forward (consumed by premises) direction

UPT_OVER_CURRENT_FORWARD_L3

0x1C

SHOULD be issued when overcurrent L3 occurs in the forward (consumed by premises) direction

UPT_OVER_CURRENT_FORWARD_L3_RTN

0x1D

SHOULD be issued when overcurrent L3 clears in the forward (consumed by premises) direction

UPT_FREQUENCY_TOO_LOW_L1

0x1E

SHOULD be issued when frequency too low L1

UPT_FREQUENCY_TOO_LOW_L1_RTN

0x1F

SHOULD be issued when frequency too low L1 clears

UPT_FREQUENCY_TOO_HIGH_L1

0x20

SHOULD be issued when frequency too high L1

UPT_FREQUENCY_TOO_HIGH_L1_RTN

0x21

SHOULD be issued when frequency too high L1 clears

UPT_FREQUENCY_TOO_LOW_L2

0x22

SHOULD be issued when frequency too low L2

UPT_FREQUENCY_TOO_LOW_L2_RTN

0x23

SHOULD be issued when frequency too low L2 clears

UPT_FREQUENCY_TOO_HIGH_L2

0x24

SHOULD be issued when frequency too high L2

UPT_FREQUENCY_TOO_HIGH_L2_RTN

0x25

SHOULD be issued when frequency too high L2 clears


Table 41—Metering LogEvents (continued)

LogEvent name

LogEvent

code

LogEvent description

UPT_FREQUENCY_TOO_LOW_L3

0x26

SHOULD be issued when frequency too low L3

UPT_FREQUENCY_TOO_LOW_L3_RTN

0x27

SHOULD be issued when frequency too low L3 clears

UPT_FREQUENCY_TOO_HIGH_L3

0x28

SHOULD be issued when frequency too high L3

UPT_FREQUENCY_TOO_HIGH_L3_RTN

0x29

SHOULD be issued when frequency too high L3 clears

UPT_GROUND_FAULT

0x2A

SHOULD be issued when ground fault occurs

UPT_GROUND_FAULT_RTN

0x2B

SHOULD be issued when ground fault clears

UPT_BURST_DETECT

0x2C

SHOULD be issued when burst detect alarm occurs

UPT_BURST_DETECT_RTN

0x2D

SHOULD be issued when burst detect alarm clears

UPT_PRESSURE_TOO_LOW

0x2E

SHOULD be issued when pressure too low

UPT_PRESSURE_TOO_LOW_RTN

0x2F

SHOULD be issued when pressure too low clears

UPT_PRESSURE_TOO_HIGH

0x30

SHOULD be issued when pressure too high

UPT_PRESSURE_TOO_HIGH_RTN

0x31

SHOULD be issued when pressure too high clears

UPT_FLOW_SENSOR_COMMUNICATION_ ERROR

0x32

SHOULD be issued when flow sensor communication error occurs

UPT_FLOW_SENSOR_COMMUNICATION_ ERROR_RTN

0x33

SHOULD be issued when flow sensor communication error clears

UPT_FLOW_SENSOR_MEASUREMENT_ FAULT

0x34

SHOULD be issued when flow sensor measurement fault occurs

UPT_FLOW_SENSOR_MEASUREMENT_ FAULT_RTN

0x35

SHOULD be issued when flow sensor measurement fault clears

UPT_FLOW_SENSOR_REVERSE_FLOW

0x36

SHOULD be issued when reverse flow is detected

UPT_FLOW_SENSOR_REVERSE_FLOW

_RTN

0x37

SHOULD be issued when reverse flow clears

UPT_FLOW_SENSOR_AIR_DETECT

0x38

SHOULD be issued when flow sensor air detect alarm occurs

UPT_FLOW_SENSOR_AIR_DETECT_RTN

0x39

SHOULD be issued when flow sensor air detect alarm clears

UPT_PIPE_EMPTY

0x3A

SHOULD be issued when pipe empty alarm occurs

UPT_PIPE_EMPTY_RTN

0x3B

SHOULD be issued when pipe empty alarm clears

UPT_INLET_TEMPERATURE_SENSOR_

FAULT

0x3C

SHOULD be issued when inlet temperature sensor fault

UPT_INLET_TEMPERATURE_SENSOR_

FAULT_RTN

0x3D

SHOULD be issued when inlet temperature sensor fault

clears

UPT_OUTLET_TEMPERATURE_SENSOR_

FAULT

0x3E

SHOULD be issued when outlet temperature sensor fault

UPT_OUTLET_TEMPERATURE_SENSOR_

FAULT_RTN

0x3F

SHOULD be issued when outlet temperature sensor fault

clears

UPT_OVER_CURRENT_REVERSE_L1

0x40

SHOULD be issued when overcurrent L1 occurs in the

reverse (supplied by premises) direction

UPT_OVER_CURRENT_REVERSE_L1_RTN

0x41

SHOULD be issued when overcurrent L1 clears in the

reverse (supplied by premises) direction

UPT_OVER_CURRENT_REVERSE_L2

0x42

SHOULD be issued when overcurrent L2 occurs in the

reverse (supplied by premises) direction

UPT_OVER_CURRENT_REVERSE_L2_RTN

0x43

SHOULD be issued when overcurrent L2 clears in the reverse (supplied by premises) direction

UPT_OVER_CURRENT_REVERSE_L3

0x44

SHOULD be issued when overcurrent L3 occurs in the reverse (supplied by premises) direction

UPT_OVER_CURRENT_REVERSE_L3_RTN

0x45

SHOULD be issued when overcurrent L3 clears in the reverse (supplied by premises) direction